7.9 Diagnosing and Resetting Faults
360
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
7.9
Diagnosing and Resetting Faults
When a fault occurs and the drive stops, do the procedures in this section to remove the cause of the fault, then re-
energize the drive.
◆
Fault Occurs Without Power Loss
WARNING!
Crush Hazard. Wear eye protection when you do work on the drive. If you do not use correct safety equipment, it can
cause serious injury or death.
WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
1.
Supply power to the control circuit from the external 24 V input.
2.
Use monitor parameters
U2-xx [Fault Trace]
to show the fault code and data about the operating status of the
drive immediately before the fault occurred.
3.
Use the information in the Troubleshooting tables to remove the fault.
Note:
1. To find the faults that were triggered, check the fault history in
U2-02 [Previous Fault]
. To find information about drive status (such as
frequency, current, and voltage) when the faults were triggered, check
U2-03 to U2-20
.
2. If the fault display stays after you re-energize the drive, remove the cause of the fault and reset.
◆
Fault Occurs Without Power Loss
1.
Examine the fault code shown on the keypad.
2.
Use the information in the Troubleshooting tables to remove the fault.
3.
Do a fault reset.
◆
Fault Reset
If a fault occurs, you must remove the cause of the fault and re-energize the drive.
lists the different
methods to reset the drive after a fault.
Table 7.3 Fault Reset Methods
Methods
Description
Method 1
While the keypad is showing the fault or alarm code, push
(Reset) or
on the keypad.
Method 2
Switch ON the MFDI terminal set to
H1-xx = 14 [MFDI Function Select = Fault Reset]
.
Note:
The default setting for
H1-04 [Terminal S4 Function Selection]
is
14 [Fault Reset]
.
Method 3
1.
De-energize the drive main circuit power supply.
2.
Energize the drive again after the keypad display goes out.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...