This function detects when PM motors are not synchronized.
The drive cannot detect when motors are not synchronized because the frequency reference is low during start up and
the motor is locked. If fault detection is necessary in these conditions, set the control fault detection level to enable
detection of desynchronization because of motor locking. Increase the setting in 5-unit increments.
■
L8-93: Low Speed Pull-out DetectionTime
No.
(Hex.)
Name
Description
Default
(Range)
L8-93
(073C)
Expert
Low Speed Pull-out
DetectionTime
Sets the length of time the drive will wait to start baseblock after detecting
LSo [Low Speed Motor
Step-Out]
.
1.0 s
(0.0 - 10.0 s)
Set this parameter to 0.0 to disable the function.
■
L8-94: Low Speed Pull-out Detect Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-94
(073D)
Expert
Low Speed Pull-out Detect
Level
Sets the detection level for
LSo [Low Speed Motor Step-Out]
as a percentage of
E1-04 [Maximum
Output Frequency]
.
3%
(0 - 10%)
■
L8-95: Low Speed Pull-out Amount
No.
(Hex.)
Name
Description
Default
(Range)
L8-95
(077F)
Expert
Low Speed Pull-out Amount
Sets the average count of
LSo [Low Speed Motor Step-Out]
detections.
10
(1 - 50 times)
◆
L9: Drive Protection 2
L9 parameters
are used to configure the protection function used to detect cooling fan faults.
■
L9-16: FAn1 Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time
Sets the detection time for
FAn1 [Drive Cooling Fan Fault]
. Yaskawa recommends that you do not
change this parameter value.
4.0 s
(0.0 - 30.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV