398
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
■
18: Torque Detection 2 (N.O.)
Setting Value
Function
Description
18
Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
ON : The output current/torque is more than the torque value set with
L6-05 [Torque Detection Level
2]
, or the level is less than the torque value set with
L6-05
for longer than the time set with
L6-06
[Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than the detection level of
L6-05
for longer than the time set in
L6-06
.
•
Refer to
“
L6: Torque Detection
”
for more information.
■
19: Torque Detection 2 (N.C.)
Setting Value
Function
Description
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with
L6-05 [Torque Detection
Level 2]
, or the level is less than the torque value set with
L6-05
for longer than the time set with
L6-
06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than the detection level of
L6-05
for longer than the time set in
L6-06
.
•
Refer to
“
L6: Torque Detection
”
for more information.
■
1A: During Reverse
Setting Value
Function
Description
1A
During reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
Figure 2.99 Reverse Operation Output Time Chart
■
1B: During Baseblock (N.C.)
Setting Value
Function
Description
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : The drive is not in baseblock.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM