Table 2.63 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67
0
A=B=1
1
A=1 or B=1
2
A=0 or B=0
3
A=B=0
4
A=B
A=B
5
A != B
6
AND(A, )
7
OR(A, )
8
-
On
Note:
•
When you use the function to output logical calculation results, you cannot set
H2-01 to H2-03 = 1xx [Inverse Output of xx]
. If you do, the
drive will detect
oPE33 [Digital Output Selection Error]
.
•
When you do not use
H2-60, H2-63, and H2-66
, set them to
F
. The through mode function is not supported.
◆
H2 MFDO Parameters
■
H2-01: Term M1-M2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
0
(0 - 1FF)
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in through mode.
■
H2-02: Term M3-M4 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
1
(0 - 1FF)
Note:
Set this parameter to
F
when not using the terminal or to use the terminal in through mode.
■
H2-03: Term M5-M6 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
2
(0 - 1FF)
Note:
Set this parameter to
F
when not using the terminal or to use the terminal in through mode.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV