401
5.8
External Interlock
For applications that will have unwanted effects on the system if the drive stops, make an interlock between fault
relay output (MA, MB, MC) and the MFDO Drive Ready signal.
◆
Drive Ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which
Drive Ready [H2-
xx = 6]
is set will enter the ON status.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
•
The drive is de-energized
•
During a fault
•
There is problem with the control power supply
•
There is a parameter setting error that will not let the drive run, although a Run command is entered
•
An overvoltage or undervoltage fault occurs when the Run command is entered
•
The drive is in Programming Mode.
◆
Interlock Circuit Example
Refer to
for an example of how two drives that run one application use the Drive Ready and Fault output
signals to interlock with the controller.
Terminal
Output Signal
Parameter Settings for Output Signal
MA, MB, MC
Fault
-
M1-M2
Drive Ready
H2-01 = 6
Figure 5.69 Interlock Circuit Example
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...