2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
325
OFF : The output frequency is less than the value of “
L4-03
-
L4-04
,” or it is not more than the value
of
L4-03
.
Figure 2.82 Example of Frequency Detection 4 (value of L4-03 Is Positive)
■
17: Torque Detection 1 (N.C.)
Setting Value
Function
Description
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque is more than
L6-02 [Torque Detection Level 1]
, or the level is less
than
L6-02
for longer than
L6-03 [Torque Detection Time 1]
.
Note:
•
When
L6-01 ≥ 5
, the drive will detect when the output current/torque is less than
L6-02
for longer than
L6-03
.
•
Refer to
L6: Torque Detection on page 389
for more information.
■
18: Torque Detection 2 (N.O.)
Setting Value
Function
Description
18
Torque Detection 2 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
ON : The output current/torque is more than
L6-05 [Torque Detection Level 2]
, or the level is less
than
L6-05
for longer than
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 389
for more information.
■
19: Torque Detection 2 (N.C.)
Setting Value
Function
Description
19
Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque is more than
L6-05 [Torque Detection Level 2]
, or the level is less
than
L6-05
for longer than
L6-06 [Torque Detection Time 2]
.
Note:
•
When
L6-04 ≥ 5
, the drive will detect when the output current/torque is less than
L6-05
for longer than
L6-06
.
•
Refer to
L6: Torque Detection on page 389
for more information.
■
1A: During Reverse
Setting Value
Function
Description
1A
During reverse
The terminal activates when the motor operates in the reverse direction.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...