228
YASKAWA
TOEPYAIGA5002A GA500 Programming
Related Parameters
Multi-Step Speed
Reference 1
H1-xx = 3
Multi-Step Speed
Reference 2
H1-xx = 4
Multi-Step Speed
Reference 3
H1-xx = 5
Multi-Step Speed
Reference 4
H1-xx = 32
Jog Reference
H1-xx = 6
Reference 14 (
d1-14
)
ON
OFF
ON
ON
OFF
Reference 15 (
d1-15
)
OFF
ON
ON
ON
OFF
Reference 16 (
d1-16
)
ON
ON
ON
ON
OFF
Jog Reference (
d1-17
)
-
-
-
-
ON
*1
The Jog Frequency Reference (JOG command) overrides all other frequency references.
Figure 2.48 Time Chart for Multi-step Speed Reference/JOG Reference
■
d1-01: Reference 1
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change. Calculate the upper limit value with this formula:
Upper limit value = (
E1-04
) × (
d2-01
) / 100
•
When
A1-02 = 6 [Control Method Selection = AOLV/PM]
, the drive sets
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
To set
d1-01
to 1-step speed parameter in a multi-step speed operation, set
b1-01 = 0 [Frequency Reference Selection 1 = Keypad]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...