TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
197
Drive Model
Screw Size
Tightening Torque
N
∙
m (lbf
∙
in)
4001 - 4012
M5
2.0 - 2.5
(17.7 - 22.1)
4018 - 4038
M5
2.0 - 2.5
(17.7 - 22.1)
◆
Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or
less as specified in UL61800-5-1.
■
Ambient Temperature
Keep the ambient temperature in this range:
•
-10 °C to +35 °C (14 °F to 95 °F)
◆
Wire the Main Circuit Terminal Block
Wire the main circuit terminal block correctly as specified by the instructions in the
manual.
To select the correct wire gauge, refer to
Main Circuit Wire Gauges and Tightening
■
Notes on Wiring the Main Circuit Terminal Block
Refer to
Notes on Wiring the Main Circuit Terminal Block on page 55
for more
information.
■
Main Circuit Wire Gauges and Tightening Torques
Refer to
Single-Phase 200 V Class on page 199
Three-Phase 200 V Class on page 201
,
and
Three-Phase 400 V Class on page 205
for the recommended wire gauges and
tightening torques of the main circuit terminals.
Comply with local standards for correct wire gauges in the region where you will use the
drive.
WARNING
Electrical Shock Hazard. Only connect factory-recommended devices or circuits to
drive terminals B1, B2, -, +1, and +2. Do not connect AC power to these terminals. Incorrect wiring can
cause damage to the drive and serious injury or death from fire.