172
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Code
Name
Causes
Possible Solutions
ndAT
Error Received Data
The parameter settings for
model and specifications (power
supply voltage and capacity) are
different between the keypad
and the drive.
1.
Make sure that drive model and the
value set in
o2-04 [Drive Model
(KVA) Selection]
agree.
2.
Restore the parameters.
The parameters are not stored in
the keypad.
1.
Connect a keypad that has the
correct parameters.
2.
Restore the parameters.
PWEr
DWEZ Password
Mismatch
The password set in the backup
operation with
qx-xx
[DriveWorksEZ Parameters]
and
rx-xx [DriveWorksEZ
Connections]
is incorrect.
Set the DWEZ PC software password
supplied by Yaskawa for the DWEZ
program user ID downloaded to the
drive.
rdEr
Error Reading Data
You tried to back up the data
when
o3-02 = 0 [Copy Allowed
Selection = Disabled]
.
Set
o3-02 = 1 [Enabled]
and back up
again.
vAEr
Voltage Class,
Capacity Mismatch
The power supply specifications
or drive capacity parameter
settings are different between
the keypad and the drive.
1.
Make sure that drive model and the
value set in
o2-04 [Drive Model
(KVA) Selection]
agree.
2.
Restore the parameters.
vFyE
Parameters do not
Match
The parameters that are backed
up in the keypad and the
parameters in the drive are not
the same.
1.
Restore or backup the parameter
again.
2.
Verify the parameters.
16
European Standards
Figure 16.1 CE Mark
The CE Mark identifies that the product meets environmental and safety standards in the
European Union. Products manufactured, sold, or imported in the European Union must
display the CE Mark.
European Union standards include standards for electrical appliances (Low Voltage
Directive), standards for electrical noise (EMC Directive), and standards for machinery
(Machinery Directive).
This product displays the CE Mark in accordance with the Low Voltage Directive, the
EMC Directive, and the Machinery Directive.