302
YASKAWA
TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Model
Terminal
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Wire
Stripping
Length
mm
Terminal Screw
Tightening
Torque
N
∙
m (in
∙
lb)
Size
Shape
B018
L/L1, N/L2
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
10
14 - 8
10
M4
1.5 - 1.7
(13.5 - 15)
-, +1
8
12 - 6
10
M4
1.5 - 1.7
(13.5 - 15)
B1, B2
14
14 - 12
10
M4
1.5 - 1.7
(13.5 - 15)
8
12 - 8
-
M5
2.0 - 2.5
(17.7 - 22.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co., Ltd.