18
YASKAWA
TOEP C710617 0SA YASKAWA AC Drive GA500 Installation Manual
◆
Derating Depending on Ambient Temperature
When you install drives in an area where ambient temperatures are higher than the rated
conditions, set
L8-12 [Ambient Temperature Setting]
and
L8-35 [Installation Method Selection]
.
Derate the output current as specified in
.
No.
(Hex.)
Name
Description
Default
(Range)
L8-12
(04B8)
Ambient
Temperature
Setting
Sets the ambient temperature of the drive installation area.
40 °C
(-10 °C - +60 °C)
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation
Method Selection
Sets the type of drive installation.
3
(0 - 3)
0 : IP20/UL Open Type
Use this setting to install IP20/UL Open Type drives.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive
and side of the enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive side-by-side.
You cannot install finless-type drives side-by-side.
2 : IP20/UL Type 1
Use this setting to install IP20/UL Type 1 drives.
You cannot install a UL Type 1 Kit (optional) on a finless-type drive.
3 : External Heatsink/Finless
Use this setting when the heatsink (cooling fin) is outside the enclosure panel or when you
install a finless-type drive.
A -
L8-35 = 3 [External Heatsink/Finless]
(default setting)
B -
L8-35 = 0 [IP20/UL Open Type]
(0.5 m/
s of airflow around the drive is
necessary)
Figure 5.5 Derating Depending on Drive Installation Method
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV