1F
Through Mode
Set this value when using the terminal in the pass-through mode.
No.
(Addr.)
Name
Description
Setting
Page
H4: Analog Outputs
H4-01
(3050H)
Analog Output 1
Monitor Selection
Sets the monitor signal from analog output 1.
Set the desired monitor parameter to the digits available in U
-
. For
example, enter “103” for U1-03.
Default: 102
Min: 000
Max: 999
H4-02
(3051H)
Analog Output 1
Gain
Sets the signal level at analog output 1 that is equal to 100% of the selected
monitor value.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H4-03
(3052H)
Analog Output 1
Bias
Sets the bias value added to analog output 1 signal.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H4-04
(3053H)
Analog Output 1
Cell Selection
Sets the number of the power cell to be output from analog output 1. This
setting is effective when 9
(Power C ell) has been set for H4-01 (Analog
Output 1 Monitor Selection).
Default: 1
Min: 1
Max: 15
H4-05
(3054H)
Analog Output 1
Signal Level
Selection
Sets the signal level output 1.
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
H4-11
(305AH)
Analog Output 2
Monitor Selection
Sets the monitor signal from analog output 2. Set this parameter to the last
three digits (
-
) of the desired U
-
parameter. Some U parameters
are available only in certain control modes.
Default: 103
Min: 000
Max: 999
H4-12
(305BH)
Analog Output 2
Gain
Sets the gain for voltage output via analog output 2.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H4-13
(305CH)
Analog Output 2
Bias
Sets the amount of bias added to the voltage output via analog output 2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
H4-14
(305DH)
Analog Output 2
Cell Selection
Sets the number of the Power Cell to be output from analog output 2. This
setting is effective when 9
(Power Cell) has been set for H4-11 (Analog
Output 2 Monitor Selection).
Default: 1
Min: 0
Max: 15
H4-15
(305EH)
Analog Output 2
Signal Level
Selection
Sets the signal level for analog output 2.
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
H4-21
(3064H)
Analog Output 3
Monitor Selection
Sets the monitor signal for output from analog output 3. Set this parameter to
the last three digits (
-
) of the desired U
-
parameter. Some U
parameters are available only in certain control modes.
Default: 000
Min: 000
Max: 999
H4-22
(3065H)
Analog Output 3
Gain
Sets the gain for voltage output via analog output 3.
Default: 100.0%
Min: -999.9%
Max: 999.9%
H3 Analog Input Settings
H3-
Setting
Function
Description
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 61 ページ 2013年10月11日 金曜日 午後8時18分