2.6 F: Option Settings
168
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
n
F4-15: Analog Output 6 (Terminal V2) Signal Level Selection
Sets the signal level for analog output 6 (terminal V2).
Setting 0: 0 to 10 Vdc
Setting 1: -10 to 10 Vdc
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Analog Output 5 (Terminal V1)
1. View the value set to F4-02 (Analog Output 5 (Terminal V1) Gain) on the digital operator. A voltage equal to 100% of
the parameter being set in F4-01 will be output from analog output 5 (terminal V1).
2. Adjust F4-02 viewing the monitor connected to the analog output 5 (terminal V1).
3. View the value set to F4-03 on the digital operator, analog output 5 (terminal V1) will output a voltage equal to 0% of
the parameter being set in F4-01.
4. Adjust F4-03 viewing the output signal on the analog output 5 (terminal V1).
Analog Output 6 (Terminal V2)
1. View the value set to F4-12 (Analog Output 6 (Terminal V2) Gain) on the digital operator. A voltage equal to 100% of
the parameter being viewed in F4-11 will be output from analog output 6 (terminal V2).
2. Adjust F4-12 viewing the monitor connected to the analog output 6 (terminal V2).
3. View the value set to F4-13 on the digital operator, analog output 6 (terminal V2) will output a voltage equal to 0% of
the parameter being set in F4-11.
4. Adjust F4-13 viewing the output signal on the analog output 6 (terminal V2).
u
F5: Contact Output Card Settings
These parameters set the drive for operation with the contact output option card DO-A3. This section describes
parameters that govern operation with a contact output option card. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F5-01 through F5-08: Contact Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below are used to assign functions to the output terminals on the
option card.
n
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card works with the drive.
Note:
Refer to TOBP C730600 41 YASKAWA AC Drive-Option Card DO-A3 Installation Manual for more details on F5-09 settings.
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
No.
Name
Setting Range
Default
F4-15
Analog Output 6 (Terminal V2) Signal Level Selection
0 or 1
1
No.
Name
Setting Range
Default
F5-01
Contact Output 1 (Terminal P1-PC Output Selection)
0 to 1FF
0: During run
F5-02
Contact Output 2 (Terminal P2-PC Output Selection)
0 to 1FF
1: Zero speed
F5-03
Contact Output 3 (Terminal P3-PC Output Selection)
0 to 1FF
2: Frequency (speed) agree
F5-04
Contact Output 4 (Terminal P4-PC Output Selection)
0 to 1FF
4: Frequency (FOUT) detection 1
F5-05
Contact Output 5 (Terminal P5-PC Output Selection)
0 to 1FF
6: Drive ready
F5-06
Contact Output 6 (Terminal P6-PC Output Selection)
0 to 1FF
37: During frequency output
F5-07
Contact Output 7 (Terminal M1-M2 Output Selection)
0 to 1FF
F: Not used
F5-08
Contact Output 8 (Terminal M3-M4 Output Selection)
0 to 1FF
F: Not used
No.
Parameter Name
Setting Range
Default
F5-09
DO-A3 Output Mode Selection
0 to 2
0
MV1000ParameterGuide_E_conditional.book 168 ページ 2013年10月11日 金曜日 午後8時18分