Specifications C - 2
Standard Drive and Bypass Specifications
The standard Drive and Bypass specifications are listed in the following tables.
208-240 VAC
Table C.1 208-240VAC Drive and Bypass Specifications
Bypass Model Number E7L_ *
D003
D004
D007
D010
D016
D024
D030
D046
D059
D074
D088
Motor HP
208V
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
-
240V
0.5/0.75
1
1.5/2
3
5
7.5
10
15
20
25
30
Bypass rated output current (A)
3.5
4.6
7.5
10.6
16.7
24.2
30.8
46.2
59.4
74.8
88
Drive Model Number CIMR-E7U
22P2
22P2
22P2
22P2
23P7
25P5
27P5
2011
2015
2018
2022
Drive rated output capacity (kVA)
1.4
1.8
3.0
4.1
6.4
8.8
12.0
18.0
23.0
29.0
34.0
Drive rated output current (A)
3.6
4.6
7.8
10.8
16.8
23.0
31.0
46.2
59.4
74.8
88.0
Drive max. output voltage (V)
3-phase; 200, 208, 220, 230, or 240VAC (Proportional to input voltage)
Drive max. output frequency (Hz)
120 Hz
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240VAC, 50/60 Hz
Rated input current (A)
4.3
5.5
9.4
13
20
24
37
53
70
89
98
Allowable voltage fluctuation
+ 10%, - 15%
Allowable frequency fluctuation
±5%
Measures for
power supply
harmonics
DC Reactor
Optional
Built-in
12-Pulse
Rectification
Not possible
Possible
Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Bypass and
Drive's rated output current is equal to, or greater than, the motor's rated current.
A phase-shifting transformer is required on the power supply for 12-pulse rectification.
* Only 208V model numbers are shown.
C
o
ntr
o
l
char
act
er
is
ti
cs
P
o
wer
s
upply
ch
ar
ac
te
ri
st
ic
s
Summary of Contents for E7LVD002
Page 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01...
Page 8: ...Introduction vi Notes...
Page 12: ...Table of Contents x Notes...
Page 54: ...Electrical Installation 2 22 Wiring Diagram...
Page 55: ...Electrical Installation 2 23...
Page 87: ...Start Up and Operation 4 9 Notes...
Page 202: ...Diagnostic Troubleshooting 6 30 Notes...
Page 248: ...Capacity Related Parameters B 6 Notes...
Page 279: ...Communications D 27 Note...
Page 280: ...Communications D 28...
Page 292: ...Spare Parts F 6...
Page 304: ...Index 12...
Page 305: ......