698
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Setting
Signal Input Method from
Peripheral Devices
External Fault Detection Method
Stopping Method
N.O.
N.C.
Always
Detected
Detected
during RUN
Only
Ramp to Stop
(Fault)
Coast to Stop
(Fault)
Fast Stop
(Fault)
Continuous
Operation
(Alarm Only)
29
-
x
x
-
-
-
x
-
2A
x
-
-
x
-
-
x
-
2B
-
x
-
x
-
-
x
-
2C
x
-
x
-
-
-
-
x
2D
-
x
x
-
-
-
-
x
2E
x
-
-
x
-
-
-
x
2F
-
x
-
x
-
-
-
x
*1
Set the terminal to N.O. (detects external fault when switched ON) or N.C. (detects external fault when switched OFF).
*2
Set the drive to always detect each fault or to detect only during run.
■
30: Light-load Accel 1 Enabled
Setting Value
Function
Description
30
Light-load Accel 1 Enabled
Enables or disables the selection of Light-Load Accel 1 Enabled function.
ON : Enabled
OFF : Disabled
Note:
Refer to
Light-load Acceleration 1 Function on page 207
for details.
■
31: Forward Travel Limit (N.O.)
Setting Value
Function
Description
31
Forward Travel Limit (N.
O.)
If you turn on a terminal while a motor rotates forward, the drive turns off the brake release command (holds the brake), the
motor coasts to stop, and the output frequency becomes 0. If you turn on a terminal while a motor rotates in reverse, the motor
will not stop.
ON : Disables the forward operation Run command.
OFF : Enables the forward operation Run command.
Note:
Refer to
Travel Limit Function on page 215
for details.
■
32: Forward Travel Limit (N.C.)
Setting Value
Function
Description
32
Forward Travel Limit (N.
C.)
If you turn off a terminal while a motor rotates forward, the drive turns off the brake release command (holds the brake), the
motor coasts to stop, and the output frequency becomes 0. If you turn off a terminal while a motor rotates in reverse, the motor
will not stop.
ON : Enables the forward operation Run command.
OFF : Disables the forward operation Run command.
Note:
Refer to
Travel Limit Function on page 215
for details.
■
33: Reverse Travel Limit (N.O.)
Setting Value
Function
Description
33
Reverse Travel Limit (N.
O.)
If you turn on a terminal while a motor rotates in reverse, the drive turns off the brake release command (holds the brake), the
motor coasts to stop, and the output frequency becomes 0. If you turn on a terminal while a motor rotates forward, the motor
will not stop.
ON : Disables the reverse operation Run command.
OFF : Enables the reverse operation Run command.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...