SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
The user can switch between 2 induction motors using an external input, and operate them. The drive saves the
control methods, V/f patterns, motor parameters, and crane sequences for 2 motors and optimizes control of both
motors.
ON : Selects motor 2
OFF : Selects motor 1
Note:
Refer to
Motor Switch Function on page 216
for details.
■
17: Fast Stop (N.C.)
Setting Value
Function
Description
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is ON while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
•
Fully stop the motor
•
Cancel the Run command
•
Cancel the fast stop command
Note:
•
To use the N.O. switch to input the fast stop command, set 15 (Fast Stop (N.O.)).
•
Refer to
C1-09: Fast Stop Time on page 603
for more information.
•
Set
C1-09 [Fast Stop Time]
to a correct deceleration time. If the deceleration time is too short, it can cause an overvoltage fault and
failure to stop the motor from coasting.
shows an example of how fast stop operates.
Figure 11.54 Fast Stop Time Chart
■
1A: Accel/Decel Time Selection 2
Setting Value
Function
Description
1A
Accel/Decel Time Selection
2
Set this function and
H1-xx = 7 [Accel/Decel Time Selection 1]
together. Sets the drive to use
Acceleration/Deceleration Time 3
[C1-05, C1-06]
or
Acceleration/Deceleration Time 4 [C1-07, C1-08]
.
Note:
Refer to
C1: Accel & Decel Time on page 600
for more information.
■
1B: Programming Lockout
Setting Value
Function
Description
1B
Programming Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
You can continue to view parameter setting values when the terminal is
OFF [Parameter Write Prohibit]
.
ON : Programming Lockout
OFF : Parameter Write Prohibit
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...