10.17 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
551
10.17 Parameters that Change from the Default Settings with
A1-02 [Control Method Selection]
The values for the parameters in these tables depend on the values for parameter
A1-02
. When you change
A1-02
,
the default settings will change.
◆
A1-02 = 0 to 4 [Induction Motor Control Methods]
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
b2-01
DC Injection/
Zero
SpeedThreshold
0.0 - 10.0
0.1 Hz
0.5
0.5
0.5
0.5
0.5
b2-04
DC Inject
Braking Time at
Stop
0.00 - 10.00
0.01 s
0.00
0.00
0.00
0.50
0.00
C1-11
Accel/Decel
Time Switchover
Freq
0.0 - 400.0
0.1 Hz
0.0
0.0
0.0
0.0
0.0
C2-01
S-Curve Time @
Start of Accel
0.00 - 10.00
0.01 s
0.20
0.20
0.20
0.20
0.20
C3-01
Slip
Compensation
Gain
0.0 - 2.5
0.1
0.0
-
1.0
1.0
0.1
C3-02
Slip
Compensation
Delay Time
0 - 10000
1 ms
2000
-
200
-
-
C4-01
Torque
Compensation
Gain
0.00 - 2.50
0.01
1.00
1.00
1.00
-
-
C4-02
Torque
Compensation
Delay Time
0 - 10000
1 ms
200
200
20
-
-
C4-13
Torque Comp
Delay Time
Select 1
0 - 60000
1 ms
200
200
20
-
20
C4-15
Torque Comp
Delay Time
Select 2
0 - 60000
1 ms
200
200
20
-
20
C4-16
Torque Comp
Delay Time
Select 3
0 - 60000
1 ms
200
200
20
-
20
C5-01
ASR
Proportional
Gain 1
0.00 - 300.00
0.01
-
0.20
-
20.00
10.00
C5-02
ASR Integral
Time 1
0.000 - 60.000
0.001 s
-
0.200
-
0.500
0.500
C5-03
ASR
Proportional
Gain 2
0.00 - 300.00
0.01
-
0.02
-
20.00
10.00
C5-04
ASR Integral
Time 2
0.000 - 10.000
0.001 s
-
0.050
-
0.500
0.500
C5-06
ASR Delay Time
0.000 - 0.500
0.001 s
-
-
-
0.004
0.004
C5-07
ASR Gain
Switchover
Frequency
0.0 - 400.0
0.1 Hz
0.0
0.0
0.0
0.0
0.0
C6-02
Carrier
Frequency
Selection
1 - F
1
1
1
1
1
1
d3-01
Jump Frequency
1
0.0 - 400.0
0.1 Hz
0.0
0.0
0.0
0.0
0.0
d3-02
Jump Frequency
2
0.0 - 400.0
0.1 Hz
0.0
0.0
0.0
0.0
0.0
d3-03
Jump Frequency
3
0.0 - 400.0
0.1 Hz
0.0
0.0
0.0
0.0
0.0
d3-04
Jump Frequency
Width
0.0 - 20.0
0.1 Hz
1.0
1.0
1.0
1.0
1.0
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...