10.12 n: Special Adjustment
◆
n1: Hunting Prevention
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
0 : Disable
1 : Enabled
2 : Enabled (High Carrier Frequency)
Determined by o2-04
(0 - 2)
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to
change this parameter.
1.00
(0.00 - 2.50)
n1-03
(0582)
Expert
Hunting Prevention
Time Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is
not necessary to change this parameter.
Determined by o2-04
(0 - 500 ms)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts
Reverse run. Usually it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
n1-08
(1105)
Expert
Current Detection
Method
Sets how the drive decreases the motor vibration that is caused by leakage current.
Usually it is not necessary to change this parameter.
0 : 2-Phases
1 : 3-Phases
0
(0, 1)
n1-13
(1B59)
Expert
DC Bus Stabilization
Control
Sets the oscillation suppression function for the DC bus voltage.
0 : Disabled
1 : Enabled
0
(0, 1)
n1-14
(1B5A)
Expert
DC Bus Stabilization
Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus
voltage. Set
n1-13 = 1 [DC Bus Stabilization Control = Enabled]
to enable this
parameter.
100.0 ms
(50.0 - 500.0 ms)
n1-15
(0BF8)
Expert
PWM Voltage Offset
Calibration
Sets the calibration method that the drive uses to decrease torque/current ripple.
0 : No Calibration
1 : One Time Calibrate at Next Start
2 : Calibrate Every Time at Start
Determined by A1-02
(0 - 2)
n1-16
(0BFB)
Hunting Prevention High
Fc Gain
Sets the gain for the hunting prevention function. This parameter functions best with a
high carrier frequency. Usually it is not necessary to change this parameter.
Determined by o2-04
(0.00 - 2.50)
n1-17
(0BFC)
Expert
Hunting Prevent High Fc
Filter
Sets the responsiveness of the hunting prevention function. Usually it is not necessary to
change this parameter.
500 ms
(0 - 1000 ms)
n1-20
(1588)
Expert
Voltage Calibration
Duration
Sets the calibration time at start. Usually it is not necessary to change this parameter.
50 ms
(10 - 500 ms)
◆
n2: Auto Freq Regulator (AFR)
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
n2-01
(0584)
Automatic Freq
Regulator Gain(F)
Sets the gain of the AFR function for forward run as a magnification value. Usually it is
not necessary to change this setting.
1.00
(0.00 - 10.00)
n2-02
(0585)
Automatic Freq
Regulator Time 1
Sets the time constant that sets the rate of change for the AFR function. Usually it is not
necessary to change this setting.
50 ms
(0 - 2000 ms)
n2-03
(0586)
Automatic Freq
Regulator Time 2
Sets the time constant to determine the variation in speed of the AFR function. Use this
parameter during regeneration. Usually it is not necessary to change this setting.
750 ms
(0 - 2000 ms)
n2-06
(1567)
Automatic Freq
Regulator Gain(R)
Sets the gain of the AFR function for reverse run as a magnification value. Usually it is
not necessary to change this setting.
1.00
(0.00 - 10.00)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...