TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Input/Output
Terminals
Power Supply Specifications
Pulse train output
MP, AC
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Pulse train input
RP, AC
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Safe disable input
H1, H2, HC
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Serial communication input/output
D+, D-, AC
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
24 V external power supply
PS, AC
Use the UL Listed class 2 power
supply.
Multi-Function Photocoupler Output
P1, C1, P2, C2
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
◆
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National
Electric Code (NEC) and the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and
L1-01 through L1-04 [Motor Overload Protection
Select]
correctly to enable motor overload and overheat protection.
Refer to the control method and set the motor rated current with
E2-01 [Motor Rated
Current (FLA)]
,
E5-03 [PM Motor Rated Current (FLA)]
, or
E9-06 [Motor Rated Current
(FLA)]
.
■
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E2-01
(030E)
Motor Rated
Current (FLA)
Sets the motor rated current in amps.
Determined by
o2-04, C6-01
(10% to 200% of
the drive rated
current)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV