YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
211
Drive Model
Semiconduc
tor Fuse
Part Number
Manufacturer:
Eaton/
Bussman
Class CC, J or
T Fuse
Maximum
Amps
MCCB
(Schneider
Powerpact
current
limiting MCCB)
Class RK5
Fuse
Maximum
Amps
Enclosure
Volume
Minimum (in
3
)
4009
FWH-80B or
FWH-90B
15
HLL36015
15
960
4012
FWH-80B or
FWH-90B
20
HLL36020
20
960
4018
FWH-80B
30
-
-
960
4023
FWH-100B
40
-
-
960
4031
FWH-125B
50
-
-
2560
4038
FWH-175B
60
-
-
2560
Electric Code Compliance
The user must provide short circuit protection to protect input branch circuits as specified
by the National Electric Code (NEC), the Canadian Electric Code, Part 1 (CEC), and local
codes.
◆
Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC),
the Canadian Electric Code, Part I (CEC), and local codes. Yaskawa recommends the
NEC class 1 circuit conductor. Use the UL approved class 2 power supply for external
power supply.
Table 17.8 Control Circuit Terminal Power Supplies
Input/Output
Terminals
Power Supply Specifications
Digital input
S1 to S7, SN, SC, SP
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Analog input
A1, A2, AC ,+V
Uses the LVLC power supply in the
drive.
Use the UL Listed class 2 power
supply for external power supply.
Analog output
AM, AC
Uses the LVLC power supply in the
drive.