![YASKAWA CIPR-GA50C series Technical Manual Download Page 700](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765700.webp)
700
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
L6-11: Mech Fatigue Hold Off Time
No.
(Hex.)
Name
Description
Default
(Range)
L6-11
(046B)
Mech Fatigue Hold Off
Time
Sets the time that the drive will start mechanical deterioration detection triggered by the
cumulative operation time of the drive.
0 h
(0 - 65535 h)
When the total operation time of the drive is more than the value set in
L6-11
, the drive will detect mechanical
weakening. Use
U4-01 [Cumulative Ope Time]
to monitor the drive total operation time.
◆
L7: Torque Limit
The torque limit function limits the internal torque reference for the drive to and keeps the torque from the motor
constant. This function limits the torque applied to loads and regenerative torque to a value less than a set
quantity. This function also prevents damage to machinery and increases the reliability of continuous operation.
You can set torque limits individually for the four quadrants, which include torque direction (motoring/
regeneration) and direction of motor rotation (forward/reverse). When the torque reference value is at the set
torque limit, the MFDO terminal set for
During Torque Limit [H2-xx = 30]
activates.
Note:
•
The drive output current limits maximum output torque. The drive limits torque to 150% of the rated output current for Heavy Duty
Rating (HD) and to 110% of the rated output current for Normal Duty Rating (ND). The actual output torque is not more than the limits
of the drive rated output current when you set the torque limit to a high value.
•
When you use torque limits for lifting applications, do not lower the torque limit value too much. When the torque limit function is
triggered, falls and rollbacks can occur because of sudden acceleration stops and stalls of the motor.
■
Configuring Settings
Use one of these methods to set torque limits:
•
Individually set the four torque limit quadrants using
L7-01 to L7-04 [Torque Limit]
.
•
Use MFAI to individually set the four torque limit quadrants. Set
H3-02, H3-10 = 10, 11, 12 [MFAI Function
Select = Forward Torque Limit, Reverse Torque Limit, Regenerative Torque Limit]
.
•
Use MFAI to set all four torque limit quadrants together. Set
H3-02, H3-10 = 15 [General Torque Limit]
.
•
Use a communication option to set all four torque limit quadrants together.
shows the configuration method for each quadrant.
Figure 12.127 Torque Limits and Analog Input Setting Parameters
Note:
•
When
L7-01 to L7-04
and analog inputs or communication option torque limits set torque limits for the same quadrant, the drive
enables the lowest value.
In this example of parameter settings, the torque limit for quadrant 1 is 130% and the torque limit for quadrants 2, 3, and 4 is 150%.
Settings:
L7-01 = 130%
,
L7-02 to L7-04 = 200%
, and MFAI torque limit = 150%
•
The drive output current limits maximum output torque. The torque limit is 150% of the rated output current for HD and to 120% of
the rated output current for ND. The actual output torque is not more than the limits of the drive rated output current when you set the
torque limit to a high value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...