12.8 H: Terminal Function Selection
624
YASKAWA
SIEPC71061753A GA500 Technical Manual
■
H2-20: Comparator 1 Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example,
set
H2-20 = 102
to monitor
U1-02 [Output Frequency]
.
102
(000 - 999)
Note:
•
For information on the comparator function, refer to
and
•
The configurable monitor changes when the control method changes.
■
H2-21: Comparator 1 Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-21
(1541)
Comparator 1 Lower Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-22: Comparator 1 Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-22
(1542)
Comparator 1 Upper Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-23: Comparator 1 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in
H2-20 [Comparator 1 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to
and
■
H2-24: Comparator 1 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
■
H2-25: Comparator 1 Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to
and
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...