12.8 H: Terminal Function Selection
614
YASKAWA
SIEPC71061753A GA500 Technical Manual
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run
Command Input Error] and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)]
.
■
42: Run Command (2-Wire Sequence 2)
Setting Value
Function
Description
42
Run Command (2-Wire
Sequence 2)
Sets the Run command for 2-wire sequence 2. Set this function and
H1-xx = 43 [FWD/REV Command (2-Wire Seq 2)]
at the
same time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)]
.
■
43: FWD/REV (2-Wire Sequence 2)
Setting Value
Function
Description
43
FWD/REV (2-Wire
Sequence 2)
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and
H1-xx = 42 [Run Command (2-Wire Sequence
2)]
together.
ON : Reverse
OFF : Forward
Note:
•
You must input the Run command to rotate the motor.
•
This function will not operate at the same time as
H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)]
.
■
44: Add Offset Frequency 1 (d7-01)
Setting Value
Function
Description
44
Offset Frequency 1
Sets the function to add the offset frequency set in
d7-01 [Offset Frequency 1]
to the frequency reference when the terminal
activates.
Note:
Refer to
“
d7: Offset Frequency
”
for more information.
■
45: Add Offset Frequency 2 (d7-02)
Setting Value
Function
Description
45
Offset Frequency 2
Sets the function to add the offset frequency set in
d7-02 [Offset Frequency 2]
to the frequency reference when the terminal
activates.
Note:
Refer to
“
d7: Offset Frequency
”
for more information.
■
46: Add Offset Frequency 3 (d7-03)
Setting Value
Function
Description
46
Offset Frequency 3
Sets the function to add the offset frequency set in
d7-03 [Offset Frequency 3]
to the frequency reference when the terminal
activates.
Note:
Refer to
“
d7: Offset Frequency
”
for more information.
■
47: Node Setup (CANopen)
Setting Value
Function
Description
47
Node Setup (CANopen)
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from the host
controller.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...