12.8 H: Terminal Function Selection
YASKAWA
SIEPC71061753A GA500 Technical Manual
613
■
35: PID Input (Error) Invert
Setting Value
Function
Description
35
PID Input (Error) Invert
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
Note:
Refer to
“
PID control block diagram
”
for more information.
■
3E: PID Setpoint Selection 1
Setting Value
Function
Description
3E
PID Setpoint Selection 1
Set this function and
H1-xx = 3F [PID Setpoint Selection 2]
together. Sets the function to switch the PID setpoint to
b5-58 to
b5-60 [PID Setpoint 2 to 4]
.
Refer to
“
b5-58 to b5-60: PID Setpoint 2 to 4
”
for more information.
■
3F: PID Setpoint Selection 2
Setting Value
Function
Description
3F
PID Setpoint Selection 2
Set this function and
H1-xx = 3E [PID Setpoint Selection 1]
at the same time. Sets the function to switch the PID setpoint to
b5-
58 to b5-60 [PID Setpoint 2 to 4]
.
Refer to
“
b5-58 to b5-60: PID Setpoint 2 to 4
”
for more information.
■
40: Forward RUN (2-Wire)
Setting Value
Function
Description
40
Forward RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 41 [Reverse Run Command (2-Wire Seq)]
at the same time.
ON : Forward Run
OFF : Run Stop
Note:
•
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm
EF [FWD/REV Run
Command Input Error]
and the motor will ramp to stop.
•
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
•
This function will not operate at the same time as
H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)]
.
Figure 12.71 2-Wire Sequence Wiring Example
■
41: Reverse RUN (2-Wire)
Setting Value
Function
Description
41
Reverse RUN (2-Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and
H1-xx = 40 [Forward Run Command (2-Wire
Seq)]
at the same time.
ON : Reverse Run
OFF : Run Stop
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...