E5: PM Motor Settings
E5 parameters
are used to set PM motor data.
Set
E5-01
to the motor code when using PM motors recommended by Yaskawa.
E5
and other related motor
parameters will be automatically set to the optimal values.
Perform Auto-Tuning for all other PM motors. If information from motor nameplates or test reports is available,
the
E5 parameters
can be manually entered.
Note:
•
The keypad shows
E5-xx
only when
A1-02 = 5, 6 [Control Method Selection = OLV/PM, AOLV/PM]
.
•
E5-xx parameters
are not reset when the drive is initialized using parameter
A1-03 [Initialize Parameters]
.
■
E5-01: PM Motor Code Selection
No.
(Hex.)
Name
Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
FFFF
(0000 - FFFF)
Note:
•
If the drive hunts or shows an alarm after you enter a motor code, use the keypad to enter the value shown on the nameplate to
E5-xx
.
•
When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set
E5-01 = FFFF
.
gives information about the motor code setting digits.
Figure 12.62 PM Motor Code
■
E5-02: PM Motor Rated Power
No.
(Hex.)
Name
Description
Default
(Range)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units from
o1-58 [Motor Power Unit Selection]
.
Determined by o2-04, C6-
01
(0.10 - 30.00 kW)
These Auto-Tuning methods will automatically set this parameter:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
•
PM Rotational Auto-Tuning
■
E5-03: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E5-03
(032B)
Motor Rated Current (FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-
01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1 A: 2056 to 2082, 4031 to 4060
The drive automatically sets
E5-03
to the value input for
T2-06 [PM Motor Rated Current]
after you do these
types of Auto-Tuning:
•
PM Motor Parameter Settings
•
PM Stationary Auto-Tuning
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...