Table 12.41 Guidelines for Carrier Frequency Parameter Setup
Symptom
Remedy
Speed and torque are not stable at low speed.
Decrease the carrier frequency.
Speed and torque are not stable at low speed.
Decrease the carrier frequency.
Too much leakage current from the drive.
Decrease the carrier frequency.
Wiring between the drive and motor is too long.
Decrease the carrier frequency.
Note:
If the motor cable is too long, it can be necessary to decrease the carrier frequency. Refer to
for the
wiring distance and decrease the carrier frequency.
Audible motor noise is too loud.
Increase the carrier frequency. Use Swing PWM.
Note:
The default carrier frequency in ND is
C6-02 = 7 [Swing PWM1 (Audible Sound 1)]
, with a 2 kHz base. You can
increase the carrier frequency in Normal Duty mode, but this will also decrease the drive rated current.
Table 12.42 Wiring Distance
Wiring Distance
50 mm (164 ft) Maximum
100 m (328 ft) Maximum
More than 100 m (328 ft)
C6-02 [Carrier Frequency Selection]
1 to F (up to 15 kHz)
1 to 2 (up to 5 kHz), 7
1 (up to 2 kHz), 7
Note:
•
When the wiring length is longer than 100 m (328 ft), set A1-02 = 0 [V/f].
•
The maximum wiring cable length between the drive and a PM motor is 100 m (328 ft).
•
If the cable length between the drive and the motor is too long when
A1-02 = 6
, set
A1-02 = 5
.
■
C6-03: Carrier Frequency Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use
C6-02
to set a carrier frequency between set selectable values, you can set the value in
C6-
03
. The carrier frequency will be fixed to the value set to
C6-03
.
When
A1-02 = 0 [Control Method Selection = V/f]
, set
C6-03 = C6-04 [Carrier Frequency Lower Limit]
to fix
the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
When
A1-02 = 0
, set
C6-03
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
as shown in
to
make the carrier frequency change linearly with the output frequency.
Figure 12.47 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
•
When
C6-05 ≤ 7
, the drive disables
C6-04
. The carrier frequency is fixed to the value set to
C6-03
.
•
The drive detects
oPE11 [Carrier Frequency Setting Error]
when these conditions are correct at the same time:
–
C6-05 ≥ 6
–
C6-04 ≥ C6-03
■
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...