When
b5-01 = 3 or 4 [Fref + PID Trim or Fref + PID Trim (D on feedback)]
, one of the inputs in
will be the PID setpoint.
Table 12.30 Input Methods for the PID Setpoint
Input Methods for the PID Setpoint
Setting Value
MFAI terminal A1
Set
H3-02 = C [Terminal A1 Function Selection = PID Setpoint]
.
MFAI terminal A2
Set
H3-10 [Terminal A2 Function Selection] = C
.
MEMOBUS/Modbus register 0006H
Sets MEMOBUS/Modbus register 000FH (Control Selection Setting) bit 1 to 1 (PID
setpoint input). Enters the PID setpoint to MEMOBUS/Modbus register 0006H (PID
Target, 0.01% units, signed).
Pulse train input terminal RP
Set
H6-01 = 2 [Terminal RP Pulse Train Function = PID Setpoint Value]
.
b5-19 [PID Setpoint Value]
Set
b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled]
. Enters the PID setpoint to
b5-
19
.
Note:
If you set two inputs for the PID setpoint, it will trigger operation error
oPE07 [Analog Input Selection Error]
.
■
Entering the PID Feedback Value
You can use two methods to input the PID feedback value to the drive. One method uses a single feedback signal
for usual PID control. The other method uses two signals. The difference between those signals sets the deviation.
•
Use a single feedback signal.
Use
to select how the feedback signal is input to the drive for PID control.
Table 12.31 PID Feedback Input Method
PID Feedback Input Method
Setting Value
MFAI terminal A1
Set
H3-02 = B [PID Feedback]
.
MFAI terminal A2
Set
H3-10 = B
.
Pulse train input terminal RP
Set
H6-01 = 1 [PID Feedback Value]
.
•
Use two signals, and use the difference between those signals as the feedback signal.
The drive uses two feedback signals, and the difference between those signals becomes the deviation.
Use
to select how the second feedback value is input to the drive. The drive calculates the deviation
of the second feedback value. Set
H3-02 or H3-10 = 16 [Terminal A1 or A2 Function Selection = Differential
PID Feedback]
to enable the second feedback signal used to calculated the deviation.
Table 12.32 PID Differential Feedback Input Method
PID Differential Feedback Input Method
Setting Value
MFAI terminal A1
Set
H3-02 = 16 [Differential PID Feedback]
.
MFAI terminal A2
Set
H3-10 = 16
.
Note:
If you set
H3-02 and H3-10 = 16
, it will trigger
oPE07 [Analog Input Selection Error]
.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...