![YASKAWA CIPR-GA50C series Technical Manual Download Page 362](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765362.webp)
362
YASKAWA
SIEPC71061753A GA500 Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F1-11
(038A)
Speed Deviation Detect
DelayTime
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in
F1-10
to cause
dEv [Speed Deviation]
.
Note:
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
0.5 s
(0.0 - 10.0 s)
F1-14
(038D)
Encoder Open-Circuit
Detect Time
Sets the length of time that the drive must not receive a pulse signal to cause
PGo
[Encoder (PG) Feedback Loss]
.
Note:
Motor speed and load conditions can cause
ov [Overvoltage]
and
oC [Overcurrent]
faults.
When
A1-02 = 0 [Control Method Selection = V/f]
, set
H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)]
to enable this parameter.
2.0 s
(0.0 - 10.0 s)
◆
F6: Communication Options
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F6-01
(03A2)
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects
bUS [Option Communication Error]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
1
(0 - 5)
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Sets the conditions at which
EF0 [Option Card External Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-03
(03A4)
Comm External Fault
(EF0) Select
Sets the method to stop the motor or let the motor continue operating when the drive
detects
EF0 [Option Card External Fault]
.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
F6-04
(03A5)
bUS Error Detection
Time
Sets the delay time for the drive to detect
bUS [Option Communication Error]
.
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
2.0 s
(0.0 - 12.0 s)
F6-06
(03A7)
Torque Reference/Limit
by Comm
Sets the function that enables and disables the torque reference and torque limit
received from the communication option.
0 : Disabled
1 : Enabled
0
(0, 1)
F6-07
(03A8)
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed reference when the
freqency reference source is NetRef or ComRef (communication option card or
MEMOBUS/Modbus communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
1
(0, 1)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized
with
A1-03 [Initialize Parameters]
.
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
0
(0, 1)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set a node address that is different than all other node addresses. Do not
set this parameter to
0
. Incorrect parameter settings will cause
AEr [Station Address
Setting Error]
errors and the L.ERR LED on the option will come on.
0
(0 - 64)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...