YASKAWA
SIEPC71061753A GA500 Technical Manual
585
The keypad shows
EF0
and the drive continues operation.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set to
Alarm [H2-01 to H2-03 = 10]
activates.
■
F6-04: bUS Error Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
F6-04
(03A5)
bUS Error Detection Time
Sets the delay time for the drive to detect
bUS [Option Communication Error]
.
2.0 s
(0.0 - 12.0 s)
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
■
F6-06: Torque Reference/Limit by Comm
No.
(Hex.)
Name
Description
Default
(Range)
F6-06
(03A7)
Torque Reference/Limit by
Comm
Sets the function that enables and disables the torque reference and torque limit received from the
communication option.
0
(0, 1)
0 : Disabled
1 : Enabled
■
F6-07: Multi-Step Ref @ NetRef/ComRef
No.
(Hex.)
Name
Description
Default
(Range)
F6-07
(03A8)
Multi-Step Ref @ NetRef/
ComRef
Sets the function that enables and disables the multi-step speed reference when the freqency
reference source is NetRef or ComRef (communication option card or MEMOBUS/Modbus
communications).
1
(0, 1)
0 : Disable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed to 16-
step speed references) and the Jog Frequency Reference (JOG command) are disabled.
1 : Enable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed through
16-step speed references) and the Jog Frequency Reference (JOG command) are enabled, and you can change the
frequency reference.
■
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name
Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize
F6-xx and F7-xx parameters
when the drive is initialized with
A1-03
[Initialize Parameters]
.
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use
A1-03
to initialize the drive, this setting will not change.
■
F6-10: CC-Link Node Address
No.
(Hex.)
Name
Description
Default
(Range)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 64)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to
0
. Incorrect parameter settings
will cause
AEr [Station Address Setting Error]
errors and the L.ERR LED on the option will come on.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...