![YASKAWA CIPR-GA50C series Technical Manual Download Page 317](http://html2.mh-extra.com/html/yaskawa/cipr-ga50c-series/cipr-ga50c-series_technical-manual_3241765317.webp)
10.5 Model Specifications (Three-Phase 400 V Class)
YASKAWA
SIEPC71061753A GA500 Technical Manual
317
10.5
Model Specifications (Three-Phase 400 V Class)
Table 10.5 Ratings (Three-Phase 400 V Class)
Model
Duty Rating
4001
4002
4004
4005
4007
4009
4012
Maximum Applicable Motor
Output
(kW)
HD
0.37
0.55
1.1
1.5
2.2
3.0
4.0
ND
0.37
0.75
1.5
2.2
3.0
4.0
5.5
Maximum Applicable Motor
Output
(HP)
HD
1/2
3/4
2
3
3
4
5
ND
1/2
1
2
3
4
5
7.5
Input
Rated Input
Current (A)
HD
1.2
1.8
3.2
4.4
6.0
8.2
10.4
ND
1.2
2.1
4.3
5.9
8.1
9.4
14
Output
Rated Output
Capacity
(kVA)
HD
0.9
1.4
2.6
3.7
4.3
5.6
7
ND
0.9
1.6
3.1
4.1
5.4
6.8
9.1
Rated Output
Current (A)
HD
1.2
1.8
3.4
4.8
5.6
7.3
9.2
ND
1.2
2.1
4.1
5.4
7.1
8.9
11.9
Overload Tolerance
•
HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
•
ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
Carrier Frequency
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
•
V/f, OLV, OLV/PM: 590 Hz
•
AOLV/PM: 270 Hz
•
EZOLV: 120 Hz
Measures for
Harmonics
DC reactor
External options
Braking Device Braking Transistor
Standard internal characteristics
EMC Filter
EMC Filter
IEC61800-3
Factory option
Models 4xxxE: Category C2 (Conducted emission)
Power Supply
Rated Voltage/Rated Frequency
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
Permitted Voltage Fluctuation
-15% to +10%
Permitted Frequency Fluctuation
±5%
Input Power
(kVA)
HD
1.1
1.6
2.9
4
5.5
7.5
9.5
ND
1.1
1.9
3.9
5.4
7.4
8.6
13
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2
The rated output capacity is calculated with a rated output voltage of 440 V.
Table 10.6 Ratings (Three-Phase 400 V Class)
Model
Duty Rating
4018
4023
4031
4038
4044
4060
Maximum Applicable Motor Output
(kW)
HD
5.5
7.5
11.0
15.0
18.5
22.0
ND
7.5
11.0
15.0
18.5
22.0
30.0
Maximum Applicable Motor Output
(HP)
HD
10
10
15
20
25
30
ND
10
15
20
25
30
40
Input
Rated Input
Current (A)
HD
15
20
29
39
50.5
59.7
ND
20
24
38
44
59.7
80.7
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...