7.7
Auto-Tuning Errors
This table gives information about errors detected during Auto-Tuning. If the drive detects an Auto-Tuning error,
the keypad will show the error and the motor will coast to stop. The drive will not send notification signals for
faults and alarms when Auto-Tuning errors occur.
Two types of Auto-Tuning errors are:
Endx
and
Erx
.
Endx
identifies that Auto-Tuning has successfully completed
with calculation errors. Find and repair the cause of the error and do Auto-Tuning again, or set the motor
parameters manually. You can use the drive in the application if you cannot find the cause of the
Endx
error.
Erx
identifies that Auto-Tuning was not successful. Find and repair the cause of the error and do Auto-Tuning
again.
Code
Name
Causes
Possible Solutions
End1
Excessive Rated Voltage Setting
The torque reference was more than 20% during
Auto-Tuning or the no-load current that was
measured after Auto-Tuning is more than 80%.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
•
If you can uncouple the motor and load, remove the motor
from the machine and do Rotational Auto-Tuning again.
•
If you cannot uncouple the motor and load, use the results
from Auto-Tuning.
Code
Name
Causes
Possible Solutions
End2
Iron Core Saturation Coefficient
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
Auto-Tuning results were not in the applicable
parameter setting range, and
E2-07
or
E2-08 [Motor
Saturation Coefficient 2]
have temporary values.
•
Examine and repair damaged motor wiring.
•
If you can uncouple the motor and load, remove the motor
from the machine and do Rotational Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End3
Rated Current Setting Alarm
The rated current value is incorrect.
Do Auto-Tuning again and set the correct rated current shown on
the motor nameplate.
Code
Name
Causes
Possible Solutions
End4
Adjusted Slip Calculation Error
The Auto-Tuning results were not in the applicable
parameter setting range.
The motor rated slip that was measured after
Stationary Auto-Tuning was 0.2 Hz or lower.
The motor rated slip that was measured after
compensation with
E2-08 [Motor Saturation
Coefficient 2]
is not in the applicable range.
The secondary resistor measurement results were
not in the applicable range.
•
Make sure the input motor nameplate data is correct.
•
Do Rotational Auto-Tuning again and correctly set the motor
nameplate data.
•
If you cannot uncouple the motor and load, do Stationary
Auto-Tuning 2.
Code
Name
Causes
Possible Solutions
End5
Resistance Tuning Error
The Auto-Tuning results of the Line-to-Line
Resistance were not in the applicable range.
•
Make sure that the input motor nameplate data is correct.
•
Examine and repair damaged motor wiring.
Code
Name
Causes
Possible Solutions
End6
Leakage Inductance Alarm
The Auto-Tuning results were not in the applicable
parameter setting range.
Make sure that the input motor nameplate data is correct, and do
Auto-Tuning again.
A1-02 [Control Method Selection]
setting is not
applicable.
•
Examine the value set in
A1-02
.
•
Make sure that the input motor nameplate data is correct, and
do Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End7
No-Load Current Alarm
The Auto-Tuning results of the motor no-load
current value were not in the applicable range.
Examine and repair damaged motor wiring.
Auto-Tuning results were less than 5% of the motor
rated current.
Make sure that the input motor nameplate data is correct, and do
Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End8
HFI Alarm
•
Inductance saliency ratio (
E5-07
/
E5-06
) is too
small.
•
The drive cannot find the
n8-36 [HFI Frequency
Level for L Tuning]
value.
•
Set the correct value on the motor nameplate to
E5-xx [PM
Motor Settings]
or do rotational/stationary Auto-Tuning.
•
When it is necessary to set
n8-35 = 1 [Initial Pole Detection
Method = High Frequency Injection]
or
n8-57 = 1 [HFI
Overlap Selection = Enabled]
, make sure that there is no
unusual noise in the low speed range (10% or less) and that the
motor does not rotate in reverse at start.
Note:
If the drive detects
End8
, it will automatically set
n8-35 =0
[Pull-in] and n8-57 = 0 [Disabled]
. Do not change the
settings unless necessary.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...