Model
Terminal
Recommended
Gauge
mm
2
Applicable Gauge
mm
2
Wire
Stripping
Length
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
Size
Shape
4060
R/L1, S/L2, T/L3
25
6 - 35
18
M5
•
≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
•
35 mm
2
≤
4.1 - 4.5
(36 - 40)
U/T1, V/T2, W/T3
16
4 - 25
18
M5
2.3 - 2.5
(19.8 - 22)
-, +1, +2
25
6 - 35
18
M5
•
≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
•
35 mm
2
≤
4.1 - 4.5
(36 - 40)
B1, B2
10
2.5 - 16
10
M4
1.5 - 1.7
(13.5 - 15)
10
6 - 16
-
M6
5.4 - 6.0
(47.8 - 53.1)
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire).
•
8-4NS from JST Mfg. Co., Ltd.
•
R8-4S from NICHIFU Co.,Ltd.
■
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. Connect semiconductor protection fuses on the input side for branch circuit protection.
Refer to
Single-Phase 200 V Class on page 169
,
Three-Phase 200 V Class on page 169
, and
for more information about recommended fuses.
WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the drive
or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators
are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of
the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you
operate the drive or peripheral devices, it can cause serious injury or death.
Three-Phase 200 V Class
Table 5.2 Factory-Recommended Branch Circuit Protection: Three-Phase 200 V Class
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2001
FWH-25A14F
2002
FWH-25A14F
2004
FWH-25A14F
2006
FWH-25A14F
2010
FWH-70B
2012
FWH-70B
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2021
FWH-90B
2030
FWH-100B
2042
FWH-150B
2056
FWH-200B
2070
FWH-200B
2082
FWH-225A
Single-Phase 200 V Class
Table 5.3 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
B001
FWH-25A14F
B002
FWH-25A14F
B004
FWH-60B
B006
FWH-80B
Drive Model
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
B010
FWH-100B
B012
FWH-125B
B018
FWH-150B
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...