SIEPC71061753A GA500 Technical Manual
135
Input Data
Parameter
Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational Auto-Tuning
(0)
Stationary Auto-Tuning
1
(1)
Stationary Line-Line
Resistance
(2)
Motor Rated Slip
Frequency
T1-10
Hz
-
x
-
Motor Iron Loss
T1-11
W
x
-
-
Test Mode Selection
T1-12
-
-
x
-
No-Load Voltage
T1-13
V
x
x
-
*1
Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*2
Input this value when
A1-02 = 0 [Control Method Selection = V/f]
.
*3
If
T1-12 = 1 [Test Mode Selection = Yes]
, when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set
E2-02 [Motor Rated Slip]
and
E2-03 [Motor No-Load Current]
.
*4
Input this value when
T1-10 [Motor Rated Slip Frequency] = 0 Hz
.
*5
Set the same value to No-Load Voltage as
T1-03 [Motor Rated Voltage]
to get the same characteristics using Yaskawa 1000-Series
drives or other legacy models.
◆
Auto-Tuning for PM Motors
This section gives information about Auto-Tuning for PM motors. Auto-Tuning sets motor parameters
E1-xx and
E5-xx
.
Table 4.9 Auto-Tuning for PM Motors
Mode
Parameter Settings
Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
Manual Entry w/ Motor Data Sheet
T2-01 = 0
•
When the information from the motor test report or motor
nameplate is available.
•
Rotational/Stationary Auto-Tuning that energizes the motor
is not done. Manually input the necessary motor
parameters.
x
x
PM Stationary Auto-Tuning
T2-01 = 1
•
When the information from the motor test report or motor
nameplate is not available.
Note:
With Stationary Auto-Tuning, the energized drive stays
stopped for approximately 1 minute. During this time, the
drive automatically measures the necessary motor
parameters.
x
x
PM Stationary Auto-Tuning for Stator
Resistance
T2-01 = 2
•
After Auto-Tuning, the wiring distance between the drive
and motor changed by 50 m (164 ft) or more.
•
When the motor output and drive capacity are different.
x
x
PM Motor Code Selection
T2-01 = 4
•
When the information from the motor test report or motor
nameplate is not available.
•
When you can decouple the motor and load and the motor
can rotate freely while Auto-Tuning.
•
The drive will automatically set the values measured during
Auto-Tuning to the motor parameters.
x
x
High Frequency Injection
T2-01 = 5
•
Automatically sets the control parameters that are
necessary to set
n8-35 = 1 [Initial Pole Detection Method
= High Frequency Injection]
or
n8-57 = 1 [HFI Overlap
Selection = Enabled]
.
•
Applicable to IPM motors only.
•
Do Auto-Tuning with the motor connected to the drive.
Note:
When you set
n8-35 = 1
or
n8-57 = 1
, do High Frequency
Injection Auto-Tuning. Set the data on the motor
nameplate to the drive before you do High Frequency
Injection Auto-Tuning. In High Frequency Injection Auto-
Tuning, the drive energizes the stopped motor and
automatically adjusts the parameters.
x
x
■
Input Data for PM Motor Auto-Tuning
To do Auto-Tuning, input data for the items in
and
that have an "x". Before starting Auto-
Tuning, prepare the motor test report or record the information on the motor nameplate as a reference.
Summary of Contents for CIPR-GA50C series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 12: ...12 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 44: ...2 9 Installation Methods 44 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 110: ...3 17 Motor Application Precautions 110 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 150: ...4 12 Test Run Checklist 150 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 156: ...5 2 European Standards 156 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 158: ...5 2 European Standards 158 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 288: ...7 10 Troubleshooting Without Fault Display 288 YASKAWA SIEPC71061753A GA500 Technical Manual...
Page 306: ...8 6 Storage Guidelines 306 YASKAWA SIEPC71061753A GA500 Technical Manual...