TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
D.2 European Standards
D.2 European Standards
Figure D.1
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling electrical noise.
This regenerative unit displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Low Voltage Directive: 2006/95/EC
• EMC Guidelines: 2004/108/EC
Devices used in combination with this regenerative unit must also be CE certified and display the CE mark. When using
regenerative unit displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user
to ensure compliance with CE standards. After setting up the device, verify that conditions meet European standards.
◆
CE Low Voltage Directive Compliance
This regenerative unit has been tested according to European standard IEC 61800-5-1, and it fully complies with the Low
Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this regenerative
unit with other devices:
■
Area of Use
Do not use regenerative unit in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with
IEC 664.
■
Standard Configuration Devices
Install appropriate standard configuration devices to the input side to protect regenerative unit wiring and prevent other
secondary damage. Select input fuses according to
for details on the regenerative unit Input Current and Rated Output Current.
NOTICE:
If a fuse is open or an Earth Leakage Circuit Breaker (ELCB) is tripped, check the wiring and the selection of peripheral
devices to identify the cause. Contact Yaskawa before restarting the regenerative unit or the peripheral devices if the cause cannot be
identified.
Table D.1 Recommended Standard Configuration Devices
Model
Three Phase Input Fuse
Three Phase Input AC
Reactor (3%L)
Three Phase Input AC
Reactor (1%L)
Fuse
Holder
SHANGHAI EAGTOP
ELECTRONIC TECHNOLOGY
CO LTD
Sao Electric Corporation
Model
Ratings
Model
Ratings
Manufacturer
Model
Ratings
Model
Ratings
200 V Class
2
03P5
350GH-20ULTC 380 V, 20 A
HT4017
400 V, 75 A
HINODE
ACL-0020-EISC
-9353BBH
264 V, 20 A,
0.53 mH
300-057-271
264 V, 15 A,
0.31 mH
2
0005
350GH-25ULTC 380 V, 25 A
HT4017
400 V, 75 A
HINODE
ACL-0030-EISC
-9353BBH
264 V, 30 A,
0.35 mH
300-057-271
264 V, 15 A,
0.31 mH
2
0007
350GH-32ULTC 380 V, 32 A
HT4017
400 V, 75 A
HINODE
ACL-0040-EISC
-9353BBH
264 V, 40 A,
0.265 mH
300-057-272
264 V, 20 A,
0.15 mH
2
0010
350GH-50ULTC 380 V, 50 A
HT4017
400 V, 75 A
HINODE
ACL-0060-EISC
-9353BBH
264 V, 60 A,
0.18 mH
300-057-273
264 V, 40 A,
0.1 mH
2
0014
350GH-63ULTC 380 V, 63 A
HT4017
400 V, 75 A
HINODE
ACL-0080-EISC
-9353BBH
264 V, 80 A,
0.13 mH
300-057-273
264 V, 40 A,
0.1 mH