This parameter table shows the most important parameters. Default settings are in
bold type
. Refer to the User Manual for a
complete list of parameters.
No.
Name
Description
A1-00
Language Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
A1-01
Access Level Selection
0: View and set A1-01 and A1-04. U
o
-
oo
parameters can also be viewed.
1: User Parameters (access to parameters
selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and
set all parameters)
3: Lock parameters
A1-02
Control Method
Selection
0: V/f Control
2: Open Loop Vector Control
A1-03
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: Terminal->Control Initialize
6008: Pressure Control
6009: Pump down level
6010: Geothermal mode
6011: VTC pressure control
6012: Pivot Panel VTC
6013: Advanced Pressure Control
6014: Pivot Panel Submersible
7770: General purpose
7771: Submersible Motor General Purpose
Note:
A1-03 is initially set to
"6008" from the factory,
although the keypad will
always display “0”.
A1-04
Enter Password
When the value set into A1-04 does not
match the value set into A1-05, parameters
A1-01 through A1-03 and A2-01 through
A2-33 cannot be changed.
A1-05
Select Password
A1-06
Application Preset
Note:
This parameter is not
settable. It is used as a
monitor only.
0: Pressure Control
1: General Purpose
2: Sub Mtr GP Oper
5: General Ext HOA
6: General HOA Keys
8: Pressure Control
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Ctl
12: Pivot Panel VTC
13: Adv PressureCtrl
14: Pivot Panel Sub
b1-01
Frequency Reference
Selection 1
0: HOA keypad
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
5: Geothermal Mode (Frequency reference
dependent on temperature input (H3-0
o
=
21)
No.
Name
Description
b1-02
Run Command
Selection 1
0: HOA keypad
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
6: A Term
7: A Serial
8: A Option
b1-03
Stopping Method
Selection
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
b1-11
Run Delay at Stop
(Back Spin Timer)
Sets the amount of time that the drive will
disallow the reapplication of the Run
command after the Run command is lost.
b1-11 is active for all b1-03 settings.
If set to zero and b1-03 = 3 (Coast to Stop
w/ Timer), a combination of C1-02 and
output frequency determine the length of
time. Otherwise, no run delay will be
applied.
b1-12
Run Delay Memory
Selection
Determines whether the Run Delay Timer
is saved to the EEPROM during power loss.
0: Disabled
1: Only at Stop
2: Running & Stop
Note:
A JVOP-183 HOA
Keypad must be plugged
into the drive for settings 1
and 2 to function. If the
keypad is removed, b1-12
will function as setting 0
(Disabled).
b1-14
Phase Order Selection
0: Standard
1: Switch phase order (reverses the
direction of the motor)
b1-15
Frequency Reference
Selection 2
0: Operator
1: Analog Input
2: Serial Communications
3: Option PCB
4: Pulse Input
b1-16
Run Command
Selection 2
Run Source 2
0: Operator
1: Digital Inputs
2: Communication
3: Option PCB
6: A Term
7: A Serial
8: A Option
b1-17
Run Command at
Power Up
0: Disregarded. A new Run command must
be issued after power up.
1: Allowed. Motor will start immediately
after power up if a Run command is
already enabled.
b5-01
PID Function Setting
0: Disabled
1: Enabled (PID output becomes output
frequency reference, deviation D
controlled)
b5-02
Proportional Gain
Setting (P)
Sets the proportional gain of the PID
controller.
b5-03
Integral Time Setting
(I)
Sets the integral time for the PID controller.
b5-06
PID Output Limit
Sets the maximum output possible from the
entire PID controller as a percentage of the
maximum output frequency.
i.8 Parameter Table
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
87