Normal PID Feedback
Input the PID feedback signal from one of the sources listed in
Table 1.20 PID Feedback Sources
PID Feedback Source
Settings
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Analog Input A3
Set H3-06 = B
Pulse Input RP
Set H6-01 = 1
Note:
A duplicate allocation of the PID feedback input will cause an oPE07 (Multi-Function Analog Input Selection Error) alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
feedback function is automatically enabled when a differential feedback input is assigned.
Table 1.21 PID Differential Feedback Sources
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16 (Differential PID Feedback)
Analog Input A2
Set H3-10 = 16 (Differential PID Feedback)
Analog Input A3
Set H3-06 = 16 (Differential PID Feedback)
Note:
A duplicate allocation of the PID differential feedback input will cause an oPE07 (Multi-Function Analog Input Selection Error) alarm.
1.2 b: Application
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
35
1
Parameter Details