2.
The drive will not allow the user to switch between LOCAL and REMOTE during run.
n
Using the LO/RE Key on the LED Operator
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press
. The LO/RE light will light up. The drive is now in Local.
To set the drive for REMOTE operation, press the
key again.
STOP
n
Using Input Terminals S1 through S7 to Switch between LO/RE
Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S7 (set the corresponding parameter
H1-01 through H1-07 to 1).
Follow the example below to set the digital input terminals.
Note:
1.
Refer to Parameter List on page 353
for a list of digital input selections.
2.
Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.
u
Parameters Available in the Setup Group
n
Setup Mode (STUP)
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently used parameters are selected
and input into Setup Mode.
1.
To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until
is displayed.
2.
Select the parameter and change the setting.
lists parameters available in the Setup group. If the desired
parameter cannot be set in the Setup mode, use the Parameter Setting mode.
Note:
1.
When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also changed automatically.
2.
Use the “Par” menu in the Programming mode to access parameters not listed in the Setup Group.
3.
Display parameters depend on A1-06.
Refer to Application Selection on page 96
.
Table 4.4 Setup Group Parameters
Parameter
Name
A1-02
Control Method Selection
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-03
Stop Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Selection
C6-02
Carrier Frequency Selection
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4
d1-17
Jog Frequency Reference
Parameter
Name
E1-01
Input Voltage Reference
E1-03
V/f Pattern Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-09
Minimum Output Frequency
E1-13
Base Voltage
E2-01
Motor Rated Current
E2-04
Number of Motor Poles
E2-11
Motor Rate Capacity
H4-02
Terminal AM Gain Setting
L1-01
Motor Protection Function Selection
L3-04
Stall Prevention Selection during Deceleration
4.3 The Drive and Programming Modes
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
89
4
Start-Up Programming & Operation