F1-10
Excessive Speed Deviation
Detection Level
Sets the allowable deviation between motor speed and
frequency reference before a speed deviation fault (dEv) is
triggered.
Set as a percentage of the maximum output frequency (E1-04).
0 to 50
10%
A
−
−
389
F1-11
Excessive Speed Deviation
Detection Delay Time
Sets the time in seconds for which a deviation between motor
speed and frequency reference has to exceed the speed
deviation detection level F1-10 before a dEv fault will occur.
0.0 to
10.0
0.5 s
A
−
−
38A
F1-14
PG Open-Circuit Detection
Time
Sets the time for which no PG pulses must be detected before
a PG Open (PGo) fault is triggered.
0.0 to
10.0
2.0 s
A
−
−
38D
F6: Serial Communications Option Card Settings
Use F6 parameters to program the drive for serial communication.
F6-01
Communications Error
operation Selection
Selects the operation after a communications error occurred.
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
4: Alarm and Run at d1-04
<9> <10>
5: Alarm and Ramp to stop
<9>
0 to 5
1
A A A
3A2
F6-02
External fault from comm.
option selection
Sets when an external fault from a comm option is detected.
0: Always detected
1: Detection during Run only
0, 1
0
A A A
3A3
F6-03
External fault from comm.
option operation selection
Selects the operation after an external fault set by a
communications option (EF0).
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
0 to 3
1
A A A
3A4
F6-04
Bus Error Detection Time
Set the delay time for error detection if a bus error occurs.
0.0 to 5.0 2.0 s
A A A
3A5
–
F6-07
<6>
NetRef/ComRef Function
Selection
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
0, 1
0
A A A
3A8
F6-08
<6>
Reset Communication
Parameters
0: Communication-related parameters (F6-
oo
and
F7-
oo
) are not reset when the drive is initialized using
A1-03.
1: Reset all communication-related parameters (F6-
oo
and
F7-
oo
) when the drive is initialized using A1-03.
0, 1
0
<1>
A A A
36A
F6-10
CC-Link Node Address
Sets the node address if a CC-Link option card is installed.
0 to 63
0
A A A
3E6
–
F6-11
CC-Link communications
speed
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
0 to 4
0
A A A
3E7
–
F6-14
BUS Error Auto Reset
Selects if a BUS fault can be automatically reset.
0: Disabled
1: Enabled
0, 1
0
A A A
3BB
–
F6-20
<7>
MECHATROLINK Station
Address
Sets the station address when the MECHATROLINK option
has been installed.
<8>
21
A A A
36B
–
F6-21
<7>
MECHATROLINK Frame
Size
MECHATROLINK-II
0: 32 byte
1: 17 byte
MECHATROLINK-III
0: 64 byte
1: 32 byte
0, 1
0
A A A
36C
–
F6-22
<7>
MECHATROLINK Link
Speed
0: 10 Mbps
1: 4 Mbps
Note:
Available only for MECHATROLINK-II.
0, 1
0
A A A
36D
–
F6-23
<7>
MECHATROLINK Monitor
Selection (E)
Sets the MECHATROLINK monitor (E).
0 to
FFFFH
0
A A A
36E
–
F6-24
<7>
MECHATROLINK Monitor
Selection (F)
Sets the MECHATROLINK monitor (F).
0 to
FFFFH
0
A A A
36F
–
B.2 Parameter Table
372