F1-10
Excessive Speed Deviation Detection Level
0 to 50%
10%
F1-11
Excessive Speed Deviation Detection Delay Time
0.0 to 10.0 s
0.5 s
n
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
No.
Parameter Name
Setting Range
Default
F1-14
PG Open-Circuit Detection Time
0.0 to 10.0 s
2.0 s
u
F6: Serial Communications Option Card Settings
These parameters configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error Operation Selection
0 to 5
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
Setting 4: Alarm and Run at d1-04
Note:
Take proper safety measures, such as installing an emergency stop switch, as the drive will continue operation when detecting an bUS error.
Setting 5: Alarm and Ramp to stop
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Selection
0 or 1
0
Setting 0: Always Detected
Setting 1: Detection During Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation Selection
0 to 3
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-07: NetRef/ComRef Function Selection
Selects how multi-step speed inputs are treated when the NetRef command is set.