4 - 37
"Contact Input Function"
This function can be set when either 1- or 2-contact input has been selected in
the additional specifications.
X: Not activated
1: External 0% lock input
Used to completely halt the flow rate signal (display, analog output, or
pulse output) at 0%.
2: External auto zero adjustment input
Enables zero adjustment from a remote location.
Zero adjustment is possible when the contact is ON for 0.2 seconds or
more.
When the contact is ON for 15 seconds or more, the status will become
ON again.
Be sure to stop the fluid.
3: External range switching input
Range No.1 or normal direction: when opened
Range No.2 or reverse direction: when closed
4: Built-in counter reset input
Effective when there is a pulse output.
Reset will take effect when the contact is ON for 0.2 seconds or more,
and counting will start from the counter reset value at the moment when
the contact turns OFF.
5: External 0% lock input and external auto zero adjustment input
Terminal ST IN1 can be set to external 0% lock input and terminal ST
IN2 to external auto zero adjustment input.
6: External 0% lock input and external range switching input
Terminal ST IN1 can be set to external 0% lock input and terminal ST
IN2 to external range switching input.
7: External 0% lock input and built-in counter reset input
Terminal ST IN1 can be set to external 0% lock input and terminal ST
IN2 to the built-in counter reset input.
8: External auto zero adjustment input and external range switching input
Terminal ST IN1 can be set to external auto zero adjustment input and
the terminal ST IN2 to external range switching input.
9: External auto zero adjustment input and built-in counter reset input
Terminal ST IN1 can be set to auto zero adjustment input and terminal
ST IN2 to built-in counter reset input.
A: External range switching input and built-in counter reset input
Terminal ST IN1 can be set to external range switching input and ter-
minal ST IN2 to built-in counter reset input.