Errors during Operation
Troubleshooting
When a problem occurs during operation, perform the following procedures.
1. Check against the table on this page for symptoms of the error. If found,
perform the steps indicated in the table.
2. When communication with S-SFC is used, read the error message and the
self-diagnostic result using the STAT (diagnosis) key.
3. When the problem cannot be solved, it is possible that the electromagnetic
flowmeter has been damaged. Contact the reference listed on the last page
of this manual.
• Make sure the electromagnetic flowmeter is
correctly grounded.
• Make sure the damping time constant is set
correctly.
• Clean the electrodes.
Output fluctuates exces-
sively beyond the estimated
flow rate range.
Trouble
Check points and treatment
• Make sure the set range is set correctly.
• Make sure the span is set correctly.
• Make sure the zero point is correctly ad-
justed.
• Make sure the converter is correctly cali-
brated.
Output exceeds 100%.
• Make sure the pipe is not empty. If it is
empty, the empty detection function will be
functioning.
• Make sure the signal line is correctly con-
nected.
• Make sure the valves are open on the upper
and lower sides.
• Make sure the span is set correctly.
• Make sure the converter is not in the con-
stant current mode.
• Make sure the flow rate is not in the low
flow cutoff range.
Output remains 0%.
Continued on next page