![Yamatake azbil FRS100 User Manual Download Page 30](http://html1.mh-extra.com/html/yamatake/azbil-frs100/azbil-frs100_user-manual_3115669030.webp)
Chapter 6. SPECIFICATIONS
■
Specifications
6-1
Rated Power Supply
100Vac 50 / 60 Hz
200Vac 50 / 60 Hz
Allowable Voltage
-15 to +10% of rated voltage
Power Consumption
7W max.
Contact Rating
250Vac (across terminals 3-4, 3-8)
Flame Sensitivity
Ignition detection level:
Flame voltage:
1V max.
Flame-out detection level:
FRS100B series flame voltage: 0.2V min.
FRS100C series flame voltage: 0.4V min.
Flame Signal Output
Use at least 0.9mm
2
wire, a max. of 5m long, with IV (indoor vinyl) insulation.
Output terminals: A (-) and B (+) on body
Input impedance of externally connected equipment: 100k
Ω
min.
Ambient Temperature
Stand-alone mounting:
-20 to +60°C
Gang mounting (2 units or more):
-20 to +45°C
Ambient Humidity
90% RH 40°C (condensation not allowed)
Vibration Resistance
4.9m/s
2
max., 10 to 60Hz for 2h each in X, Y and Z directions (when directly
mounted on panel)
Insulation Resistance
50M
Ω
min. between terminals and ground terminal by 500Vdc megger
Dielectric Strength
No failure after applying 1500Vac for 1min or 1800Vac for 1s between terminals
and ground terminal (excluding flame detector input of terminals 5 and 6)
Lightning surge
10kV, 1.2 x 50µs (JEC-187, surge impedance 75
Ω
or more) when the following
surge absorber is attached to a power supply contact (terminal 2) and the ground
terminal:
• Recommended surge absorber: 83968019-001
Life
100,000 operations (at room temperature and humidity, and rated voltage)
Body Color
Gray
Mounting
Mounted on DIN rail or screw mounted (when using the FRS50A100 subbase)
Mass
FRS100B:
Approx. 270g
FRS100C:
Approx. 270g
FRS50A subbase : Approx. 70g
Optional Parts
Subbase
Model No.: FRS50A100
(sold separately)
Flame Simulator for C7035A, C7027A Model No.: 1231514B
Lightning surge absorber
Model No.: 83968019-001
Flame Meter
Model No.: FRS60A
Flame Simulator for Flame Rod
Model No.: 123514A, 121708