Termination Code Table
15
Chapter 4. COMMUNICATION PROCEDURE
When an error occurred in the application layer, an abnormal termination code is returned as a response message.
■
Normal and warning termination
■
Error termination
Termination
Type
Contents and action
code
00
Normal
Communications end normally.
21
Alarm
Wrote data in the address that could not be set in the
communication due to the setup allotment by external
switching inputs.
The controller continues the process without writing any in the
concerned address.
23
Alarm
The controller stops reading due to access to the address
outside the scope.
The controller stops writing due to access to the address
outside the scope, however writes inside addresses.
Termination
Type
Contents and action
code
40
Error
“W” has not been set at the address.
All messages are aborted.
41
Error
“WS”, or “RS” has not been set.
All messages are aborted.
43
Error
ETX(03H) is not set in the correct position.
“,” is not set after the address.
All messages are aborted.
46
Error
The address is erroneous.
All messages are aborted.
47
Error
There is an error in the number of word addresses to read.
All messages are aborted.
48
Error
There is an error in the written numeric.
Write has been executed, except for the error address.
99
Error
An undefined command or other message error.
All messages are aborted.
Summary of Contents for Azbil CMQ-V Series
Page 43: ...35 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Page 44: ...36 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Page 45: ...37 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Page 46: ...38 Chapter 6 COMMUNICATION PROGRAM FOR MASTER STATION ...
Page 52: ......
Page 54: ......
Page 55: ......