Problem
Causes
Solutions
Line LED flickers
AC grounding wire abnormal
Check grounding wire with
assistance of power engineering
service
After AC connected to UPS,
alarm sounds short and
fast beeps and UPS shut
down
AC abnormal
Check AC power
After starting the UPS,
alarm sounds short beeps
continuously, then the UPS
shuts down
AC noise or environment
noise
Check AC or battery wires
UPS PCB abnormal
Call for service
Five short beep
continuously
Internal over temperature
Check the ventilation
Fan fail
Call service to replace the fan
Four short beep
continuously
PFC over load protect in
action due to low AC input
Check input AC power or release
LINE LED did not lit on
after connect AC input and
BOOST, INV LED lit on
with three short beep
continuously
AC input is abnormal due to
input voltage and UPS goes
into DC mode
Disconnect input AC power and
check
Input switch not turn on
Turn on the input switch