Problem
Causes
Solutions
UPS no reaction while AC
is connected
Fuse at rear panel blown
Replace fuse
No AC input
Check AC power
UPS fault
Call for service
Battery damaged
Call service to replace batteries
UPS no reaction while AC
is connected, yet DC starts
after pushing power on/off
switch
Fuse at rear panel blown
Replace fuse
No AC input
Check AC power
UPS fault
Call for service
UPS goes into DC mode
connected to AC
AC voltage or frequency
abnormal
Check AC power
UPS AC detecting circuit
fails
Call for service
UPS still in bypass mode
after de-green mode
function
UPS still in POWER OFF
status
Press power on/off key,
Buzzer sound once and the UPS
Become normal
Keys on front panel don’t
work
UPS is proceeding
controlling process
Wait for a while to operate the UPS
Key damaged
Call for service
Press FUNCTION key in
AC mode, but the UPS goes
back to AC mode within
less than 10 seconds
Internal battery
deteriorated
Call service to replace batteries
Fault LED lit
UPS abnormal
Call for service
Output load abnormal or
short circuited
Check load
Battery cannot provide
normal back up power
when there is no AC input
Internal battery
deteriorated
Call service to replace batteries
Batteries not fully charged
Charge the battery
Battery charger damaged
Replace charger and charge the
battery if necessary