background image

c).

If the Control Panel successfully receives the signal, the panel will respond accordingly to indicate the

completion of the learning-in process. Please refer to the manual of the panel.

Step.4

When the 6-minute warming period is over, one short beep will sound to indicate that the Smoke Detector

is  starting calibration process. The  process  will  be  repeated  every 100  sec  and  notified  by  a short  beep
respectively. The completion of calibration process will be notified by a 2-tone beep and the LED will be
turned off.

Normally  it  takes  about  2  ~  16  minutes  to  do  the  calibration. However, after 16 minutes,  if  the  Smoke
Detector  gives  out  continuous  beeps  instead,  it  indicates  that  the  Smoke  Detector  is  failed in  the
calibration and its battery should be removed to silence the beeps.    Then, start from step 1 to try again
after a pause of at least 30 seconds.

<

<

N

N

O

O

T

T

E

E

>

>

During the  calibration  period,  pressing  the  Test  Button  is  prohibited.  If  you  are  not  able  to  do  the  learning
process (Step 3) during the 6-minute warming period, you are requested to do the learning process after the
calibration period (Step 4).

Step 5.

After  the  completion  of  the  warming  and  calibration  process,  put the  Control  Panel  into  “

Walk  Test

mode. Then, decide upon a suitable location for the Smoke Detector’s installation and from there, press
the Test button to confirm this location is within signal range of the Control Panel.

Step 6.

Using the bracket as a template, drill two holes in the exact location, the device is
to be mounted and insert the dowels.

Step 7.

Screw  the  bracket  on  with  the  two  hooks  facing  down  by  using  the  screws  and
screwing them into the dowels.

Step 8.

Locate the single line mark on the detector and line it up with one of the hook of
the bracket. After both hooks fits in the two mounting holes on the detector, rotate
the detector counter-clockwise to lock it in onto the bracket. The installation is now
completed.

T

T

e

e

s

s

t

t

i

i

n

n

g

g

t

t

h

h

e

e

S

S

m

m

o

o

k

k

e

e

D

D

e

e

t

t

e

e

c

c

t

t

o

o

r

r

By pressing the Test button on the Smoke Detector, you can test if the Smoke Detector is functioning normally.

If the Smoke Detector functions normally, the LED will be on for 2 Sec. then it will sound a 2-tone beep.

If the buzzer sounds 3 times of 2-tone beep, which means the “

Optical Chamber

” on the Smoke Detector is

either dirty or out-of-order.

If the LED doesn’t light and no beep is sounded, it means the Smoke Detector is out-of-order.

S

S

u

u

p

p

e

e

r

r

v

v

i

i

s

s

o

o

r

r

y

y

S

S

i

i

g

g

n

n

a

a

l

l

After  installation,  the  Smoke  Detector  will  automatically  transmit  Supervisory  Signals  periodically  to  the
Control Panel at intervals of 60 min. to 100 min. randomly.

If  the  Control  Panel  has not  received  the  signal  from  the  Smoke  Detector  for  a  preset  period  of  time,  the
Control  Panel  will  indicate  it  on  its  display  to  show  that  particular  Smoke  Detector  is  experiencing  an
out-of-signal problem.

D

D

e

e

t

t

e

e

c

c

t

t

i

i

n

n

g

g

t

t

h

h

e

e

S

S

m

m

o

o

k

k

e

e

Once the concentration of the smoke exceeds the set threshold value, the Smoke Detector lights up its LED
to indicate it’s sending the Smoke Alarm signal to the Control Panel. After the transmission is completed, the
Smoke Detector then activates its buzzer with LED flashing rapidly for 10 seconds for local warning.

After this 10-second local warning period, the Smoke Detector proceeds to perform a follow-up smoke check.
If the smoke concentration is found to be alarming still, the Smoke Detector will repeat another 10 seconds
of local warning with buzzer and rapid flashing LED.

The Smoke Detector will repeatedly perform follow-up checks until the smoke concentration is lower than the
set value, then the alarm will be stopped automatically or the alarm can be stopped manually by using the

Alarm Silence

” function.

Once a Smoke Alarm Signal has been transmitted, the Smoke Detector will continue to send alarm signals
every  2  minutes  when  the  smoke  concentration continues to  be  higher  than  allowed.    This  2-minute  cycle
will  be  repeated  until  the  smoke  concentration  is  lower  than  the  set  value,  then  the  alarm  will  be  stopped
automatically or the alarm can be stopped manually by using the “

Alarm Silence

” function.

A

A

l

l

a

a

r

r

m

m

S

S

i

i

l

l

e

e

n

n

c

c

e

e

Once the alarm is sounding, pressing the Test button will put the Smoke Detector into Alarm Silence mode
for 10 min. and the alarm will be stopped.

During this 10-min. Alarm Silence period, the LED will flash once per second.

After  this  10-min.  period  is  over,  the  Smoke  Detector  will  sound  a  2-tone  beep  and  then returns  to  normal
operation  mode.  If  the  Smoke  concentration  is  still  over  the  set  threshold  value,  the  Smoke  Detector  will
sound the warning alarm again.