13. Max Reboot Attempts:
After the device has been re-booted this number of times without any successful pings, it is
assumed that there are problems with the device and WebRelay
TM
will no longer attempt to re-boot
the device. At this point, WebRelay
TM
will leave the device on but will disable the auto re-boot
feature. The auto re-boot feature will remain disabled until a user enables it through the control
page or WebRelay
TM
is powered down and powered up once again. This number can be set between
1 and 255.
The following parameters (14-19) are available when WebRelay
TM
is set to either
Standard
or
Automatic Reboot
relay mode.
14. Remote Relay Options:
The optically-isolated input can be configured to control a WebRelay
TM
device at a remote location.
The ‘Remote Relay Options’ setting is used to specify if and how the input affects the remote relay.
The options in the drop down list are described below. Note that in all cases, input changes will
only affect the remote relay at the time the input is changed. Once the change has taken place the
state of the input has no effect on the state of the remote relay (unless Keep Alive is set to
Yes (TX
State
). In other words, if the input causes the remote relay to go on, a user may turn the remote
relay off from the web browser, even if the local input is still on.
-no remote relay control-
The input has no effect on the remote relay.
-
remote command equals input
-
When a voltage is applied to the input, a command is sent to the
remote WebRelay
TM
to set the relay state to
on
. When a voltage is removed from the input,
a command is sent to the remote WebRelay
TM
to set the relay state to
off
.
-
remote command opposite of input
-
When a voltage is applied to the input, a command is sent to
the remote WebRelay
TM
to set the relay state to
off
. When a voltage is removed from the
input, a command is sent to the remote WebRelay
TM
to set the relay state to
on
.
-send on command when input on (no off command)-
When a voltage is applied to the input, a
command is sent to the remote WebRelay
TM
to set the relay state to
on
. When a voltage is
removed from the input, no commands are sent to the remote WebRelay
TM
.
-send on command when input off (no off command)-
When a voltage is removed from the input,
a command is sent to the remote WebRelay
TM
to set the relay state to
on
. When a voltage
is applied to the input, no commands are sent to the remote WebRelay
TM
.
-send off command when input off (no on command)-
When a voltage is removed from the input,
a command is sent to the remote WebRelay
TM
to set the relay state to
off
. When a voltage
is applied to the input, no commands are sent to the remote WebRelay
TM
.
-send off command when input on (no on command)-
When a voltage is applied to the input, a
command is sent to the remote WebRelay
TM
to set the relay state to
off
. When a voltage is
removed from the input, no commands are sent to the remote WebRelay
TM
.
-send pulse command when input on-
When a voltage is applied to the input, a command is sent to
the remote WebRelay
TM
to pulse the relay. When a voltage is removed from the input, no
commands are sent.
-send pulse command when input off-
When a voltage is removed the input, a command is sent to
the remote WebRelay
TM
to pulse the relay. When a voltage is applied to the input, no
commands are sent.
-send pulse command when input changes-
When a voltage is applied to the input or removed
from the input, a command is sent to the remote WebRelay
TM
to pulse the relay.
-send toggle command when input on-
When a voltage is applied to the input, a command is sent
to the remote WebRelay
TM
to toggle the relay (change the remote relay to the state opposite
of its current state). When a voltage is removed from the input, no commands are sent.
-send toggle command when input off-
When a voltage is removed the input, a command is sent to
the remote WebRelay
TM
to toggle the relay (change the remote relay to the state opposite of
its current state). When a voltage is applied to the input, no commands are sent.
-send toggle command when input changes-
When a voltage is applied to the input or removed
from the input, a command is sent to the remote WebRelay
TM
to toggle the relay (change
the remote relay to the state opposite of its current state).
Xytronix Research & Design, Inc.