pHix® Compact uncut cable-end with one, respectively two, signal outputs.
Extending the signal cable
There are no specific demands to the cable that may be used for extending the
existing cable, except that it should be shielded and that the voltage drop
should not be too big.
Note!
pHix® Compact is a passive transmitter. Considerations should be taken
regarding the voltage drop over the signal cable.
The supply voltage on the site must not drop below 12 V DC at maximum
current (20 mA.)
In order not to compromise operational reliability, the cables should be
interconnected by means of a watertight connection box (item no. 200590).