Xylem LOWARA F 1-2 Operating And Maintenance Instructions Manual Download Page 5

Caution

This booster set is an automatic machine; the pumps may start up automatically without
prior warning.
The set contains pressurised water; reduce the pressure to zero before servicing.

Maintenance

Routine check (6 monthly intervals)

1. Check all pumps produce the correct pressure.
2. Check that the pump operates without undue noise or vibration.
3. Check the break tank is clean and that the correct water level has been maintained.
4. Check that all screws are tight on electrical components.

5. Check that the earth connections are tight and making good contact.
6. Check that the gas pre charge is at the correct pressure, this should be done by isolating the vessel
from the system and draining water out of the vessel via the isolation valve drain point.
Once the water has been discharged, a tyre gauge can be connected to the pre charge valve to display the
vessel pre charge pressure. Recharge as necessary with Nitrogen or dry air.
Any other expansion vessels connected to the system can be checked in the same manner.
Clean any filters that may be connected to suction/discharge lines and ensure the mesh is in good condition.

General fault finding guide

5

Fault

Possible Cause

Remedy

Pump fails to start

Power supply failure
Control panel fuse blown
MCB tripped
Low water level

Reinstate incoming power supply
Replace power supply fuse
Reset MCB
Reinstate water supply

Pump fails to stop

Set point set too high
System pressure low due to
large leak

Lower set point
Switch unit off until leak is repaired

Pump switches on and off
quickly

Air in system
Vessel pre-charge incorrect

Purge air from pumps and pipework
Check vessel pre-charge and Charge as
necessary with Nitrogen or dry air

Pump runs but will not make
pressure

Pump air locked
Non-return valve jammed
Passing too much water

Open pump bleed screw and vent pump
Clean/replace valve
Check system for leaks

Pump overheating

Pump partially seized

Remove pump and check for foreign 
objects

Pump set frequently
starting. (pressure falls to
cut in point)

Newly installed system with
large amount of air in pipe work
Leaks in system pipe work
Vessel pre-charge incorrect

Bleed system to remove air
Repair leaks
Isolate vessel and pre-charge with 
Nitrogen as appropriate

Break tank overflowing

Leaking ball valve
Non-return valve letting by

Replace ball valve seal
Replace/clean non-return valve

Pump leaks water

Defective mechanical seal
Undue mechanical stress on
pump

Replace seal
Support the pipe work

mini f booster set o and m instructions:Layout 1

09/05/2012

15:38

Page 5

Summary of Contents for LOWARA F 1-2

Page 1: ...e noncompliance would affect safety Safety instruction where electrical hazard is involved Safety instruction where noncompliance could cause damage to the equipment Instruction for safe us This product has been designed for boosting cold water in potable water installations to the operating conditions shown This product should not be installed until this leaflet has been studied carefully and und...

Page 2: ...r full load current of all pumps as they are able to operate at the same time Motor ratings are shown on the set duty plate All non power cable should be limited to 1 5mm All connections must be made using the appropriate wiring drawings for the equipment being installed with particular attention being paid to the supply voltages The supply voltage is shown on the set duty plate Never operate this...

Page 3: ...to match the pumps fitted If pressure switch settings need altering they should be adjusted as follows Read in conjunction with fig A P1s pump 1 stop pressure which is normally set to 0 5 bar below Pmax pump closed valve head P2s pump 2 stop pressure which is normally set to 1 bar below Pmax when fitted P1 pump 1 differential pressure which is normally set at 1 bar this will start pump one 1 bar b...

Page 4: ... has been signalled to start it will run for a minimum of 90 seconds default setting even if the demand has cessed The next time the pressure falls the pumps will have been rotated so the opposite pump will be the first to operate If a low level in the break tank occurs all pumps will be stopped until the water supply has been reinstated the pumps will then be automatically released to resume norm...

Page 5: ...sible Cause Remedy Pump fails to start Power supply failure Control panel fuse blown MCB tripped Low water level Reinstate incoming power supply Replace power supply fuse Reset MCB Reinstate water supply Pump fails to stop Set point set too high System pressure low due to large leak Lower set point Switch unit off until leak is repaired Pump switches on and off quickly Air in system Vessel pre cha...

Page 6: ...UK Tel 01297 630230 Fax 01297 630270 e mail lowaraukenquiries xyleminc com http www lowara co uk http completewatersystems com Lowara is a trademark of Xylem Inc or one of its subsidiaries 2011 Xylem Inc Lowara reserve the right to make modifications without prior notice cod UKLIT0088 P05 12 Model type Order Code Pump type Serial number Installation date System set point Booster set notes mini f b...

Reviews: