Troubleshooting of alarms and errors
Code Description
Cause
Solution
A03
Derating
Temperature too high
•
Lower the room temperature
•
Lower the water temperature
•
Lower the load
A05
Data memory alarm Data memory corrupted
1. Reset the default parameters using parameter
P68
2. Wait 10 s
3. Restart the pump
If the problem continues, contact Xylem or the
Authorised Distributor
A06
LOW alarm
Lack of water detection (if P48=
ALR)
Check the water level in the system
A15
EEPROM write
failure
Data memory damaged
Stop the pump for 5 minutes and then restart it
again; if the problem continues, contact Xylem or
the Authorised Distributor
A20
Internal alarm
E01
Internal
communication error
Internal communication lost
Stop the pump for 5 minutes and then restart it
again; if the problem continues, contact Xylem or
the Authorised Distributor
E02
Motor overload error High motor current
E03
DC-bus overvoltage
error
DC-bus overvoltage
Check:
•
the system configuration
•
the position and integrity of the check valve or
the flap valve
E04
Rotor blocked
•
Motor stall
•
Loss of rotor synchronism or
rotor blocked by external
materials
•
Check that there are no foreign bodies
preventing the pump from turning
•
Stop the pump for 5 minutes and then start it
again
If the problem continues, contact Xylem or the
Authorised Distributor
E05
EEPROM Data
memory error
EEPROM Data memory
corrupted
Stop the pump for 5 minutes and then restart it
again; if the problem continues, contact Xylem or
the Authorised Distributor
E06
Grid voltage error
Voltage supply out of operating
range
Check:
•
the voltage
•
the connection of the electric system
E07
Motor winding
temperature error
Motor thermal protection trip
•
Check for impurities near the impeller and rotor.
Remove them if necessary
•
Check the conditions of installation, and the
water and air temperature
•
Wait for the motor to cool down
•
If the error persists, stop the pump for 5
minutes and then start it again
If the problem continues, contact Xylem or the
Authorised Distributor
E08
Power module
temperature error
Frequency converter thermal
protection trip
Check the conditions of installation, and the air
temperature